Eaton Tripp Lite Series SmartOnline 6000VA 5400W 208V Online Double-Conversion UPS with Maintenance Bypass - L6-20R/L6-30R Outlets, L6-30P Input, Network Card Included, Extended Run, 3U Rack/Tower - UPS - 5.4 kW - 6000 VA - VRLA - with SUPDMBP6K maintenance bypass
Device Type
UPS - rack-mountable / external
Rack Size
19" - 3U
Weight
111.55 lbs
Input Wiring
1-phase
Input Voltage
AC 200/208/220/230/240 V
Output Voltage
AC 200/208/220/230/240 V ± 1%
Power Capacity
5.4 kW / 6000 VA
Input Connectors
1 x hardwire
Output connectors
2 x power NEMA L6-20R (surge) ¦ 2 x power NEMA L6-30R (surge)
Battery
Expandable valve regulated lead-acid (VRLA)
Run Time (Up To)
3 min at full load
Networking
RS-232, USB
Remote Management Protocol
SNMP
Included Accessories
4-post rail kit, mounting hardware, cable gland
Dimensions (WxDxH)
17.3 in x 34 in x 5.1 in
Environmental Standards
ENERGY STAR
Manufacturer Warranty
2-year warranty
Bundled with
SUPDMBP6K maintenance bypass
General
Device Type
UPS - rack-mountable / external
Height (Rack Units)
3U
Rack Size
19"
Bundled with
SUPDMBP6K maintenance bypass
Expansion / Connectivity
Interfaces
1 x USB - 4 pin USB Type A ¦ 1 x console - Micro-USB 2.0 ¦ 1 x management - RJ-45 ¦ 1 x management (RS-232) - 9 pin D-Sub (DB-9) ¦ 1 x management (USB) - USB 2.0 type B ¦ 1 x battery detection - RJ-11 ¦ 1 x RPO - 3 pin terminal block ¦ 1 x ROO - 3 pin terminal block ¦ 1 x contacts - 9 pin D-Sub (DB-9)
Expansion Slots
1 (total) / 1 (free) x expansion slot
Manufacturer Warranty
Service & Support
Limited warranty - 2 years
Miscellaneous
Included Accessories
4-post rail kit, mounting hardware, cable gland
Cables Included
Power cable 10 ft ¦ USB cable - external ¦ Serial cable - external
Rack Mounting Kit
Included
Equipment Protection Value
250000 US Dollars
Features
Surge protection, VMware Ready, metal housing, cisco compatible, audible alarm, emergency power off, LCD display, Automatic Voltage Regulation (AVR), LED indicators, built-in bypass switch, cold-start function, cooling fan, Eco-Mode, remote reboot, double conversion
Compliant Standards
cUL, NOM, FCC, RoHS, EN 62040-2
Networking
Remote Management Interface
RS-232, USB
Remote Management Protocol
SNMP
Environmental Parameters
Min Operating Temperature
32 °F
Max Operating Temperature
104 °F
Humidity Range Operating
0 - 95% RH (non-condensing)
Sound Emission
45 dBA
Battery
Type
Expandable
Technology
Valve regulated lead-acid (VRLA)
Voltage Provided
180 V
Run Time (Up To)
3 min at full load ¦ 8 min at half load
Transfer Time
0 ms
Features
Hot-swappable
Power Device
UPS Technology
On-line
Supported Power Modules Qty
4
Input Voltage
AC 200/208/220/230/240 V
Frequency Provided
50/60 Hz
Input Wiring
1-phase
Frequency Required
50/60 Hz
Input Connectors
1 x hardwire
Power Output Connectors Details
2 x power NEMA L6-20R (surge) ¦ 2 x power NEMA L6-30R (surge)
Output Voltage
AC 200/208/220/230/240 V ± 1% - 50/60 Hz
Power Capacity
5.4 kW / 6000 VA
Output Waveform
Sinewave
Surge Suppression
Yes
Surge Response Time
0 ms
Efficiency
93% at 100% Load, 98% at 100% Load Eco mode
Power Factor (PF)
0.9
Total Harmonic Distortion (THD)
2 %
Dimensions & Weight
Width
17.3 in
Depth
34 in
Height
5.1 in
Weight
111.55 lbs
Dimensions & Weight (Shipping)
Shipping Width
28.5 in
Shipping Depth
38 in
Shipping Height
21.7 in
Shipping Weight
133.82 lbs
Sustainability Information
ENERGY STAR
Yes
Related Products